Work described
From the filing22kw Generac Guardian Series Generator - Supply and install a Generac 22kw standby natural gas generator. - Supply and install a pre-cast concrete pad for mounting of generator on front, right corner of home near electric and gas meters. - Supply and install a Service Entrance rated, 200-amp automatic transfer switch (ATS). - Mount ATS or emergency disconnect on exterior wall near electric meter. - Supply and install service cable to ATS. - Re-feed main breaker panel with 200-amp sub-feeder. - Rewire main breaker panel as a sub-panel with grounds and neutrals separated. - Supply all required grounding and bonding of service. - Supply and install 100-amp sub-feeder from generator to ATS. - Supply Belden communication cable from ATS to generator. - Supply a 15-amp, 120-volt circuit for trickle charger.