Work described
From the filingSETTING A 500 AG LP TANK BEHIND THE SHED THAT HAS NOT ELECTRICITY. SETTING A 24KW GENERAC GENERATOR ABOUT 30FT TO THE RIGHT OF THE SHED. RUNNING 1 INCH POLY IN A TRENCH TO THE GENERATOR WITH 2 RISERS. TRANSITION TO 1 INCH BLACK PIPE TO THE GENERATOR WITH SHUT OFF AND FLEX CONNECTOR. MC ELECTRICAL OF PLAINVILLE WILL PERFORM ALL THE NECESSARY ELECTRICAL WIRING FOR THE GENERATOR. THEY WILL PULL THEIR OWN PERMIT. TRENCHING BY OTHERS. I HAVE INCLUDED THE GENERATOR LOAD CALCS WITH THIS APPLICATION. Your application for a Building Permit has been reviewed for compliance with the 2022 State of Connecticut Building Code. The permit for the proposed work is approved. All work is subjected to field inspections. Comments below are to be reviewed and followed. 1. LP tanks are to be installed at proper distances to any building openings and/or ignition sources. NFPA 58 6.4.4.3 table 2. Provide proper separation distance from any building and property lines. NFPA 58 6.4.1.1