Work described
From the filingDirect replacement of (1) Fujitsu Heat Pump condenser model number AQU45RLXFZ and (4) wall hung evaporator coil Your application for a Building Permit has been reviewed for compliance with the 2022 State of Connecticut Building Code. The permit for the proposed work is approved. All work is subjected to field inspections. Comments below are to be reviewed and followed. 1. Installation manual for wall unit evaporator unit is required to be uploaded to portal before final inspection. IMC 304.1 2.Indoor wall unit is required to have a water sensor on condensate pan. This can either be built in unit or a separate device. IMC 307.2.3.1 2. Heating and cooling equipment and appliances are to be sized to meet supplied heat loss report. Along with follow ACCA Manual S or Manual J methodologies calculations. IMC 312.1 3. Appliance installation is to follow all manufacturer’s instructions. IMC 304.1