Work described
From the filing****DAVE IS ASSIGNED TO THIS**** COMMERCIAL Replace in like kind all upright heads in bld. Add 4 pendant heads. Replace/upsize 3/4-inch pipe to 1 inch. Cap up at main old unnecessary 5-inch feed in rear of building piped down wall. Perform 5-year FDC pressure test & internal obstruction investigation. Add new flow switch on riser and 2 os&y tamper switches to partner with new FA system. Demo now unneeded water motor gong. Perform annual system inspection and tag system.