***MIKE IS ASSIGNED TO THIS**** Removing (2) RTUs (RTU-14 and RTU-16) and replacing with VRF and ERVs. RTU-14 feed (60A) was not sufficient for VRF condenser, replacing with 90A feed. RTU-16 feed was oversized (100A) for VRF condenser, reconfiguring for 90A feed. Installing new circuits for (2) ERVs, 1 @ 15A, 1 @ 30A. Installing (2) new circuits for supplemental duct heaters, 1 @ 20A, 1 @ 80A. Adding (1) convenience outlet on roof at RTU-16. Installing (1) 15A circuit for all indoor VRF equipment. All new circuits to be in EMT conduit. Cost of electrical work was carried in mechanical permit, M-26-31084.