WE PROPOSE TO INSTALL A NEW CUSTOM COMFORT 18,000 BTU HPER HEAT AND COOLING UNIT WITH TWO 9,000 BTU LOW STATIC UNITS FOR THE TWO BEDROOMS OVER THE GARAGE. THE CONDENSER LOCATION WILL BE NEXT TO THE EXISITNG UNIT OUTSIDE AND CANNOT BE SEEN FROM THE STREET. Your application for a Building Permit has been reviewed for compliance with the 2022 State of Connecticut Building Code. The permit for the proposed work is approved. All work is subjected to field inspections. Comments below are to be reviewed and followed. 1. Separate electrical permit is required to be applied for. IRC R105.1 2. Indoor wall unit is required to have a water sensor on condensate pan. This can either be built in unit or a separate device. IRC M1411.3.1.1 3. Heating and cooling equipment and appliances are to be sized to meet supplied heat loss report. Along with follow ACCA Manual S or Manual J methodologies calculations. IRC M1401.3 4. Appliance installation is to follow all manufacturer’s instructions. IRC M1401.1